Natural oscillation case ND_7 (Back to the homepage)
This case contains two sources, i.e. generators 45 and 159, with different contributions into a single unstable local mode.
System model:
Disturbance:
Small signal analysis:
Figure 1. WECC 179-bus power system
The specifics of the cases ND_6 and ND_7 is as follows. Sensitivity of real part of the associated eigenvalue to variation of damping coefficient D for generator 159 is two times higher than that for generator 45. Thus, the contribution in negative damping of generator 159 is twice comparing to generator 45 in case ND_7 despite they have the same values of D.