This case contains two sources, i.e. generators 36 and 45, contributing two different unstable local modes.
System model:
All generators are in GENCLS model.
Parameter D for generators 36, 45 and 159 equals -1, -2.5 and 1, respectively.
Parameter D for all other generators equals 4.
All loads are in constant MVA model.
Disturbance:
A three-phase short circuit is added at bus 159 at 0.5s and cleared after 0.05s.
Small signal analysis:
The local mode at 1.41Hz has a negative damping of -0.22%.
The local mode at 1.27Hz has a negative damping of -1.06%.
Figure 1. WECC 179-bus power system